Simultaneous Display of W, A, V ( PF or Hz )
True RMS V, A, W
Auto Calibration Via Computer
Max. / Min. / Hold Function
High Immunity to External Noise
CT Ratio (1 ~ 9999)
PT Ratio (1 ~ 9999)
Option : RS-232C or RS-485 Interface
VOLTAGE |
Range |
5V, 10V, 20V, 40V, 80V, 160V, 320V, 640V total 8 ranges by auto-range or manual |
Measurement Type |
True rms |
Input Resistance |
>1M¥Ø |
Maximum Input Voltage |
1000V (peak), 700V (rms) |
PT Ratio Setting |
1 ~ 9999 |
Accuracy(at 23¡ÆC+5¡ÆC) (Sinewave) |
+ 0.1% of reading + 0.1% of range |
CURRENT |
Range |
160mA, 320mA, 640mA, 1.280A, 2.560A, 5.120A, 10.24A, 20.48A total 8 ranges by auto-range or manual |
Measurement Type |
True rms |
Input Resistance |
0.01¥Ø |
Maximum Input Current |
30A (peak), 20A (rms) |
CT Ratio Setting |
1 ~ 9999 |
Accuracy(at 23¡ÆC+5¡ÆC) (Sinewave) |
+ 0.1% of reading + 0.1% of range |
WATT |
Measurement Range |
0.32mW ~13.10kW |
Measurement Type |
True rms |
Accuracy (at 23¡ÆC+5¡ÆC) (Sinewave) |
+ 0.2% of reading + 0.2% of range |
POWER FACTOR |
Range |
0.001 ~ 1.000 |
Computation |
W / (V x A) = Power Factor (PF) |
FREQUENCY |
Measurement Range |
40Hz ~ 400Hz |
Accuracy(23¡ÆC+5¡ÆC) |
+ 0.2% of reading+2 digits |
GENERAL |
Display |
4 digits 0.56" LED and 2 sets of 4 digits 0.4" LED |
Minimum Input |
2% of range |
Response Time |
2 cycles/sec |
Overload Indicating |
" O.L " |
POWER SOURCE |
|
|
AC 100 ~ 230V, 50/60Hz |
ACCESSORIES |
|
|
Instruction manual ¡¿ 1, Power cord ¡¿ 1, Option£ºRS-232C or RS-485 Interface (Factory Installed) |
DIMENSIONS & WEIGHT |
|
251(W) ¡¿ 91(H) ¡¿ 291(D) mm Approx. 1.6kg |
|